High Temperature Investigation at Prospect Park

Liam O’Connor

10 February 2026

Summary

Investigated high return temperatures on stored hot water, found issues with dead leg and TMV.

Areas Inspected

Water temperature readings

ALARM

High return temperatures observed.

Hot water storage

ALARM

Checked conditions; high temperatures noted.

Cold water storage

OK

Checked conditions; no issues noted.

Dead legs

INTERVENTION REQUIRED
  • Dead leg present

Found a dead leg on secondary return; temporary fix applied.

TMV condition

INTERVENTION REQUIRED
  • TMV running hot

TMV was running hot; flushed line and adjusted TMV.

Actions Done On Site

Actions for Service Provider

Actions for Client

Quote Required

work needed for future approval

Item Quantity Priority
Remove redundant dead leg 1 Medium
Replace faulty TMV on basin 1 High

Invoice Items

work completed and parts used

Item Quantity
Service call-out 1
Labour for site visit 1
Temperature probe caps for testing 1